Tips for Protecting Cooling Systems

Winter puts industrial cooling systems through their paces, increasing risk of downtime. Fortunately, Summit Process Cooling is on hand with top tips for protecting cooling systems during cold snaps.

As temperatures fall, industrial cooling systems face increased pressure from freezing conditions, corrosion risk and bacterial growth. Glycol plays a critical role in protecting chilled water circuits through the winter months, yet it is often overlooked until a problem occurs. Carrying out a structured glycol check before colder weather sets in can help prevent breakdowns, protect equipment and maintain stable production.

Confirm your glycol concentration
The first and most important step is to verify glycol concentration. For UK conditions, a concentration of around 25 – 30% is typically required to provide freeze protection down to approximately -12°C to -16°C. Concentrations below this level significantly increase the risk of freezing and can encourage bacterial growth.

Check for dilution or contamination
Over time, systems that are regularly topped up can become diluted without operators realising. Water ingress, corrosion products or biological contamination can all reduce freeze protection and thermal efficiency. Visual checks are useful here. Healthy glycol should be clear, consistent in colour and free from odour or suspended particles. Investigate any deviation.

Inspect strainers, filters and pipework
Strainers and filters naturally collect debris, rust flakes and organic matter. Before winter, these should be cleaned or replaced to maintain proper flow and prevent restrictions. Pipework should also be checked for signs of corrosion or small leaks, both of which can lead to unnoticed dilution of the glycol mix.

Validate the true freeze point
Even when concentration appears correct, the actual freeze point should be confirmed. Different glycol types behave differently, meaning concentration alone is not always a reliable indicator. A handheld refractometer or test kit can quickly verify true freeze protection and highlight any discrepancies.

Review the glycol type in use
It is important to ensure the correct glycol is being used for the application. Mono Ethylene Glycol offers excellent heat transfer performance, while Propylene Glycol is often chosen where lower toxicity is required. DTX glycol provides a non-toxic alternative with strong inhibitor protection. Mixing glycol types or using an unsuitable product can compromise system protection and shorten fluid life.

Top up correctly and watch for bacteria
If adjustments are required, always top up with the same inhibited glycol type. Using incompatible fluids can accelerate corrosion. If glycol concentration has dropped below 20% at any stage, bacterial activity may already be present, with symptoms such as cloudy fluid, odour, sludge formation or reduced flow.

A thorough winter glycol check provides confidence that cooling systems are ready for colder conditions. For processors seeking additional reassurance, Summit Process Cooling supports customers with a proactive approach that helps protect assets, maintain performance and reduce the risk of unexpected downtime when temperatures drop.