Variable Frequency Drives (VFDS) are crucial for regulating electric motor speeds, but they generate electrical disturbances that must be mitigated. In this article, electronics manufacturer REO UK explores the function, benefits and design considerations of input chokes in VFD applications.
VFDs have become indispensable in modern industrial applications, providing precise control over motor speed and torque while improving efficiency and energy savings. However, VFDs introduce certain electrical disturbances, including high-frequency radio frequency interference (RFI) and harmonic distortion. These disturbances must be effectively managed to comply with regulatory standards and maintain system performance. One of the most effective solutions for mitigating power quality issues associated with VFDs is using mains chokes, also known as line chokes or line reactors. These passive components are usually manufactured from copper and electrical grade steel and are connected in series with the mains supply. They reduce harmonic distortion, limit inrush currents, and protect electrical equipment from transients.
Understanding variable frequency drives
VFDs regulate electric motors’ speed by varying the supplied power’s frequency and voltage. They typically consist of three primary sections:
- Rectifier stage: converts incoming AC power to DC.
- DC bus: filters and stores DC energy.
- Inverter stage: converts DC power back into AC with a variable frequency and voltage, which controls the motor speed.
While VFDs improve motor control and efficiency, the conversion process generates significant electrical noise and harmonic distortion. These harmonics can lead to excessive heating in electrical components, increased losses, and disturbances in nearby equipment, making power quality management a critical consideration.
The role of input chokes
Input chokes are passive inductive components installed in series between the power supply and the VFD, usually constructed from copper windings and a laminated iron core. Once installed, they require no maintenance and will tend to last as long as the installation is required to operate. Their primary function is to introduce impedance into the electrical system, which helps control the flow of harmonic currents and protect sensitive components. The key benefits of input chokes include:
- Harmonic mitigation
VFDs, being non-linear loads, generate harmonic currents that distort the power supply waveform. These harmonics can cause overheating in transformers, cables, and other electrical equipment, leading to system inefficiencies and failures. By increasing line impedance, input chokes reduce the magnitude of harmonic currents and improve overall power quality.
- Inrush current reduction:
VFDs can draw large inrush currents upon startup, causing sudden voltage dips and stressing electrical components. Input chokes limit the rate of change of current (di/dt), thereby controlling inrush currents and preventing damage to the VFD and associated equipment.
- Transient protection:
Voltage spikes and transients, which can occur due to switching events or external disturbances, pose a risk to VFDs and connected motors. Input chokes act as buffers, absorbing and dampening these transients to enhance system reliability.
Benefits of using input chokes
Incorporating input chokes into VFD systems provides several advantages:
- Improved power quality: by filtering harmonics and transients, input chokes ensure a cleaner power supply, reducing interference and improving system stability.
- Extended equipment life: reducing electrical and thermal stress on VFDs, motors, and other components prolongs their operational lifespan, reducing maintenance and replacement costs.
- Enhanced motor performance: a smoother current and voltage profile leads to more stable motor operation with less noise and vibration, improving efficiency and longevity.
- Regulatory compliance: many industrial standards, such as IEEE 519, limit harmonic distortion levels. Input chokes help meet these requirements, avoiding penalties and operational disruptions.
- Reduced RMS current and energy consumption: input chokes contribute to reducing root mean square (RMS) current, which translates into lower energy consumption and cost savings.
Design considerations for input chokes
Selecting and implementing input chokes requires careful consideration of several factors:

Inductance value:
- Input chokes are typically rated to cause a voltage drop between 2% and 4% on the line voltage. This rating significantly impacts harmonic reduction and RMS current levels.
- As illustrated in Figure 1, a 22 kW VSD without a choke exhibits high harmonic distortion, while using 2% and 4% chokes reduces Total Harmonic Current Distortion (THDi) by approximately 19% and 36%, respectively.
Voltage and current ratings:
- The choke must be rated to handle the maximum expected voltage and current without excessive heating or voltage drop.
- Undersized chokes can overheat and fail, while oversized chokes may be unnecessarily expensive.
Thermal management:
- Proper ventilation or cooling must be ensured to prevent overheating. Water-cooled chokes can be viable in environments with space constraints or controlled ambient temperatures.
Installation location:
- Chokes should be placed close to the VFD to minimise impedance mismatches and ensure optimal performance.
- High ingress protection (IP54 or greater) units allow standalone drives to be mounted in control rooms without additional enclosures.
Energy consumption and cost savings
Input chokes improve energy efficiency in VFD applications by reducing harmonic and overall RMS currents. Lower RMS current results in:
- Reduced heat generation in electrical components.
- Lower energy losses, contributing to long-term operational cost savings.
- Improved system reliability and performance.

As shown in Figure 2. a 2% input choke can lower RMS current by 8.7%, while a 4% choke achieves a reduction of 17.2%, This significant decrease translates into lower power consumption and improved efficiency across the electrical network.
To quantify the financial benefits, consider the following examples based on standard drive sizes:
- 11 kW Drive: Annual savings of £574.2 (2% choke) and £1135.2 (4% choke).
- 50 kW Drive: Annual savings of £2610.0 (2% choke) and £5160.0 (4% choke).
- 160 kW Drive: Annual savings of £8352.0 (2% choke) and £16512.0 (4% choke).
These savings are based on an assumption of 4,000 operating hours per year and an electricity cost of £0.15 per kWh, demonstrating the significant economic advantages of implementing input chokes in VFD applications.
Conclusion
Input chokes are essential in VFD applications, addressing key challenges such as harmonic distortion, inrush current and transient voltage spikes. By improving power quality, extending equipment life and enhancing motor performance, input chokes contribute to the efficiency and reliability of industrial electrical systems. Proper selection and implementation are crucial for maximising these benefits and ensuring compliance with industry standards. Under optimal conditions, input chokes can achieve a 17% reduction in input current, leading to substantial energy and cost savings over time.