Demystifying the 87Hz Characteristic

The three-phase squirrel-cage induction motor was first developed in the late 1880’s and has since been widely used in industry as the prime mover for most applications, wherever rotary or linear movement is required. As much as 67% of all electricity consumed in industry is used for running these motors, which indicates the scale of their importance.

Originally these motors were connected direct-on-line (DOL) and ran at a fixed speed until the late 1960’s when frequency inverters were developed, giving the ability to vary the speed of an electric motor. At that time, there were issues with reliability due to the motor’s insulation system being insufficient to withstand the higher pulse voltages of frequency inverters, as well as the motor’s misapplication, where the system performance was being compared to other variable speed technology such as DC motors and controllers, which operated under different principles. These issues have long since disappeared, and the three-phase squirrel-cage induction motor and frequency inverter drive system are regarded as highly reliable and flexible with now more than 50% of all motors being driven by frequency inverters.

Technology doesn’t stand still; advances in materials, efficiencies, design and knowledge have enabled the humble three-phase motor and inverter combination to solve the many challenges thrown at them in the quest for higher torques, wider speed ranges, more compact dimensions, to name a few.

As already noted, three-phase squirrel-cage induction motors can be connected directly to the line (DOL) supply and operated at a constant voltage and frequency, producing an almost constant, fixed speed drive. When started DOL, the motor has no ramp and accelerates as fast as it can, taking its full starting current every time, which can be as much as 7 x nominal current, it then runs at fixed speed. When supply is disconnected, the motor coasts to a standstill. Alternatively, they can be connected to a frequency inverter and operated with a variable voltage and variable frequency supply, providing an adjustable ramp up, variable speed capability, and an adjustable ramp down.

Field weakening

The operating behaviour of a motor changes when it is connected to a frequency inverter. The frequency inverter is connected to the AC supply and produces a variable voltage and variable frequency, supplied to the motor. Discounting any voltage boost, auto boost or sensorless vector adjustments, the output voltage and frequency increase proportionally to what is called “the rated frequency” (i.e., what the motor is expecting), in this case 400V at 50Hz.

Fig 1

In simple terms, because the voltage and frequency are proportional the motor operates with a constant flux, this relationship produces a constant torque range from the motor up to 50Hz. When using an inverter, it is possible to drive in excess of 50Hz, however, the voltage remains the same as the supply, therefore above 50Hz the volts/Hz relationship is no longer the proportional. This is called “field weakening” and it occurs when the power remains constant but the torque drops away. as shown in Fig 1.

When operating the motor in the constant torque range up to 50Hz, it is important to consider that the motor fan is providing less cooling as the motor runs at a slower speed. An old rule of thumb was that running below 20Hz with constant torque would require forced cooling (assuming 40 deg C ambient). However, with today’s minimum IE3 or higher efficiency motors that run more efficiently and hence cooler, many suppliers claim constant torque down to 10Hz (5:1 speed range) without any additional cooling is possible.

87Hz characteristic

It is perfectly acceptable to use the motor in the field weakening area provided the motor develops enough torque for the application. There is, however, another possibility: the so-called 87 Hz characteristic.

Field weakening of a motor starts if the output voltage of the frequency inverter can no longer be increased – however, its frequency is increased. What is needed should this occur is a wider range where the voltage and frequency can stay in proportion.

Fig 2

To illustrate this, take a motor (generally 4 Pole 1500 r/min) with a 230/400V 50Hz winding, which is standard for motor frame sizes up to and including IEC100 (some motor manufacturers offer this to much larger frame sizes), and connect it in a delta configuration for the 230V winding, then connect this to a 400V inverter but set the rated frequency to 87Hz, the result is a volts/frequency relationship that is proportional up to 400V 87Hz. However, at 50Hz it reaches 230V and is therefore suitable for a 230V 50Hz motor winding, this can be seen in Fig 2 – the original 230V 50Hz in red and the 400V 87Hz in blue.

Fig 3

As the voltage and frequency are proportional (constant flux), it results in constant torque from zero to the 87Hz or typically 2600 r/min motor speed. The same comments regarding cooling apply, i.e., with the new IE3 motors running down to 10Hz, delivering constant torque without any additional cooling. As a result, the motor can be run from 10Hz to 87Hz constant torque without any additional cooling, a comparison between the 50Hz and 87Hz performance can be seen in Fig 3.

When applying the 87Hz characteristic, the frequency inverter and motor must be appropriately selected, dimensioned and parameterised.

Fig 4

Considering the motor, given the torque now remains constant until 87Hz the power of any given motor increases by √3. For example, a 1.5kW 4 pole motor becomes a 2.61kW motor as shown in the table (Fig 4); the torque remains constant to 87Hz and then moves into the field weakening area.

The resulting inverter should be a 3 Phase 400V input inverter and selected based on the motor current for the 230V winding – in general it will also match the resulting power @ 87Hz.

Application benefits

Depending on the application, there are several benefits from utilising the 87Hz characteristic. The main benefit being constant torque over a much wider speed range and above the 87Hz it can still be used in the field weakening range.

By running at a higher speed, it is possible to use a higher ratio reduction/gearbox to achieve the desired machine speed. The mechanical advantage of the ratio provides a higher output torque, therefore it may be possible to reduce the original motor size selection. This is particularly interesting where many plants are looking to reduce the number of variants that they have on site.

If the application involves moving a high inertia, the reflected load inertia to the motor shaft is reduced by the ratio squared. Therefore, having a higher gearbox ratio reduces the reflected inertia and results in the system being more dynamic.

Using the 87Hz characteristic is interesting for many reasons and does offer in many cases significant benefits, but there is nothing special in terms of its set-up; it takes a standard three-phase squirrel-cage induction motor and a standard three-phase 400V input frequency inverter.